Guodian Nanjing Automation Co., Ltd.

(0)

Contact Us

Contact
  • Address: No. 8, Spark Road, Pukou Hi-tech District, Nanjing City, Jiangsu Province, China
  • Tel: +86-25-51859229
  • Fax: +86-25-51859207
  • E-mail:
Home >>WBKQ-01B High-speed Busbar Transfer Device for Back-up Power
Prev|Next

WBKQ-01B High-speed Busbar Transfer Device for Back-up Power

  • Product Details
  • Make an Inquiry

Product overview:
   This device applies to the normal manual transfer, accident transfer and abnormal operation condition transfer between service power supply with functions of post acceleration of independent back-up branch and over current protection. It adopts the technology of automatic tracking and sampling of the voltage frequency of bus ( effective measuring range is 15
55Hzas well as the unique software phase measuring technology, which effectively improve the measuring precision of the residual voltage of bus and resolves the defect of the low speed of hardware phase meausring. It provides effective guarantees for the safe and reliable transfer, especially for the accident transfer.


Main Characteristics:
 32-bit single-chip,fast operation speedstable and reliable performance;
 14-bit A / D converter with high performance, fast converting speed;
 Automatic frequency tracking technology, which ensures efficiency and high precision during width measurement, frequency measurement and phase measurement
 Field programmable logic chip FPGA with high reliability
 320 × 240 dot-matrix LCD graphic display with large screen
 Large-capacity memory chips which can record all information of device during the transfering process, and can be printed or be analyzed after upload to computer
 Maintenance-free design; no adjustable equipments in the entire device;
 Suitable to wide range of temperatures; safely operate on the environment of -20+60;
 High anti-interference performance


Main Technical Parameters
 Power supply of deviceDC220V or 110V -20% +15%
 Rated AC parameter: Voltage:100V Frequency:50HZ
 Power consumption:
   DC circuit
≤10W
   AC voltage circuit
≤0.3VA/Phase
   AC current circuit
≤0.3VA/Phase
 Over loading characteristics
AC current circuit:
    The device can continuously operate under the electric current that is twice as much as that of rated current.
    The device can continuously operate 10S under the electric current that is ten times as much as that of rated current.
    The device can continuously operate 1S under the electric current that is forty times as much as that of rated current.AC voltage circuit:
    The device can continuously operate under the voltage that is 1.5 times as much as that of rated voltage
 Precise working scope of sampling circuit:
    Current
0.2A 100.0A
    Voltage
0.5V 150.0V
    Frequency
15.0HZ 55.0HZ
    Phase angle
0.0° 360.0°
 Contact rating
    Signal circuit
carrying capacity 2A ;arc interruption capacity 60VA
    Exit circuit
DC220V 5A
 Measuring precision
    Current
Voltage):≤2
    Frequency
≤0.1HZ
    Phase angle
≤0.2°
 Switching time
    Minimum power-off time of simultaneous switching
10mS+Closing time of back-up switch + delay time set by users- tripping time of working switch
    Power-off time of Tandem Switching
10mS + tripping time of working switch+ Closing time of back-up switch
SOEDPI 1mS

Main Functional Configuration:
 Manual two-way switching between working and back-up powers under normal conditions;
 One-way switching from working power to back-up power under failure or non-normal conditions;
 Four switching methods of fast, simultaneous capture, residual voltage and long time delay to be selected
 Introduction of current auxiliary criterion can effectively prevent device from mistakenly starting as a result of contact badness of auxiliary connecting point of working branches and ensure the device of correct decoupling.
 Unique voltage lockout feature, which can lock and switch when the main wires go through a sharp drop of voltage
 Post acceleration of independent back-up branch and over-current protection
 Two-stage timing low-voltage load shedding function
 High pressure side switch hot back-up/cold back-up
 Automatic lock for the repairing of PT cars of bus, and other functions related to the voltage of bus
 PT power-off alarm and other kinds of locks
 Perfect functions of wave record for troubles
 GPS time checking and various communicating methods

 