Product overview
     DGT801 Series Digital Generator-transformer Unit Protection Device is applicable for fossil-fired or hydropower generator-transformer unit with the capacity of no more than 1000MW and the voltage class of no higher than 750kV and various wiring connection, and also applicable for protection for generator, main transformer, station transformer, HV start-up & stand-by transformer, excitation transformer (exciter), large synchronous condenser and electromotor, meeting the requirements of automation system in the power plant.
    DGT801A, DGT801B, DGT801C, DGT801D, DGT801E, DGT801F, as the serial products of DGT801, the modes of their hardware and software are absolutely the same. The only differences are the number of hardware resources and LCD size on the cabinet. Please refer to the appendix for more details. Highly reliable parallel processing technology with double power and double CPUs is adopted in them, with advanced structure, good performance, personalized debugging and maintenance, as well as reliable and safe service.
    The protection software of the DGT801A, B, C, D, E and F are absolutely the same, and completely modular, solidifying all the protections necessary for the unit in the programmable chips. By means of flexible configuration by graphic definition software, the DGT801 series devices will satisfy the configuration requirements for protection of generator-transformer units of various sizes. 

Appendix Brief introduction of DGT 801series digital generator-transformer unit protection device:

Device model

DGT801A

DGT801B

DGT801C

DGT801F

DGT801E

DGT801D

Characteristics of hardware configuration

inverse power supply

3

3

2

2

2

2

Number of protective CPU

2

2

2

2

2

2

Number of managed CPU

1

1

1

1

1

1

True color LCD

True color

True color

True color

True color

Blue screen

Blue screen

Operational mode

Touch

Touch

Touch

Touch

Key-press

Key-press

Cabinet size

10U

12U

6U

6U

6U

6U

Protection interface resources

Number of

Analog input

30

60

30

0

15

15

Number of output tripping

4×4

4×6

4×4

4×4

4×4

4×2

Number of signal

8×6

8×6

8×4

8×4

8×4

8×2

Number of protective

clip plate

4×6

4×6+10×2+4×2

4×4

42

4×4

42

32

32

switch quantity

by

hardware

4×2

4×2

4

4×2/4×3

8×2

/

switch quantity

by

software

12

8×2

8

8×2/8×3

4×4+16

4×2

Main characteristics
 Double CPUs parallel processing mode
    The hardware structures of the protection system with double powers and double CPUs are two systems which are absolutely the same but mutually exclusive. Each CPU system owns an independent power module, which realizes a separate circuit system; the parallel processing technique with a organic unity of highly reliable double CPUs, perfect self-check and mutual check function and reliable fault tolerant technique avoids the phenomena of error operation and refusing operation successfully.
 Hardware platform with high performance
n
     Main elements are of industrial standards with the core elements of military standard, which ensure the high quality of the protection device.
 Complete protection functions, flexible and reliable protection configuration
     Methods “highly modular protection”+ “graphic configuration
n options” are created originally in this device, by which the protection modular in different units can be configured according to needs through one software version, absolutely safe and reliable.
 New theories and techniques are adopted for protection
    For example: artificial neuron network technique
n based on protection theory, quasi wavelet, predictive waveform and square wave, adaptive technology, integrated protection, dot product, gradual hyperbola, fast algorithm, robustness technique which resists highly TA saturation and waveform technology as well.
     Lots of advanced techniques are adopted in the software
n design.
 Technologies of NT time sharing system, class design and
n object-oriented software design increase greatly the security and reliability of software protection.
 Fully transparent protector
    Clear indication of
n the signal outputs reflects the action status in the complete set of protector visually; protective clip plate (soft clip plate) and output clip plate are set separately with clear status indication;
    It is easy and convenient,
n complete visualization in the protector, with friendly human-machine interface, true-color liquid crystal display on big screen, rich display content of Chinese presentation, touch screen or touch mouse action.
 Powerful communication function
    It is equipped with RS-485 port, 100M Ethernet network
n communication port, to communicate with DCS or special management system in the power plant, upward the relevant information and messages; supports the communication protocols of IEC60870-5-103 and MODBUS as well as DGT801 custom communication protocol; provides networking operation management system based on WINDOWS, which is to be switched in MIS system in the power plant. It is equipped with powerful fault wave record function, with the wave data compatible with IEEE COMTRADE standard format.
 GPS time-setting methods: external idle
n contact time-setting, absolute time-setting message in RS-485 and absolute time-setting message in monitoring system.
 Electromagnetic compatibility
    It meets the highest grade of the relevant national standards.


Main protection functions
 Differential protections for both generator and transformer
 Special stator inter-turn protection
 Double frequency stator grounding protection
 Ground fault protection features of injected single flow rotor
 Impedance round type loss of excitation protection, new type inverse reactive criterion loss of excitation protection
 Double-shielding type loss of synchronism protection
 Backup protection for inter-phase short circuit
 Well equipped protection, such as over-excitation protectionInadvertent Energizing Protection which are the necessary protections for large units.
Main technical parameters
 Parameters for mechanical and operational environment


Structure size of the cabinet:
    DGT801A type: 482.6mm (length) X 370.0mm (depth) X 444.0mm (height)
    DGT801B type: 482.6mm (length) X 370.0mm (depth) X 533.0mm (height)
    DGT801C type: 482.6mm (length) X 370.0mm (depth) X 266.0mm (height)
    DGT801D type: 241.3mm (length) X 370.0mm (depth) X 266.0mm (height)
    DGT801E type: 482.6mm (length) X 370.0mm (depth) X 266.0mm (height)
    DGT801F type: 482.6mm (length) X 370.0mm (depth) X 266.0mm (height)
 ambient temperature:   -5 to +45ºC
-10 to +55ºCn
 relative
n humidity: 5%--95%
 Atmospheric pressure:   70--106kPa, 80--106kPa
n
 Rated electric parameters
    Auxiliary AC power: voltage 220V, allowable deviation
n -15% to +10%; Frequency 50Hz.
    DC power: 220V, 110V; allowable deviation-20%
n to +15%
    Alternating current: 5A, 1A; Frequency 50Hz
n
    Alternating
n voltage: 100V,  V; Frequency 50Hz.
 Power consumption
    Alternating
n current circuit: 0.5VA/phase
    Alternating voltage circuit:
0.25VA/phase (ifn U=Un)
    DC power circuit:
50W (normal); 80W (protectionn action)
 overload rating
    Alternating current circuit: 2In- runs for
n long range; 30In-10s allowable; 50In-1s allowable.
    Alternating voltage
n circuit: 1.5Un--allows to work continuously.
    DC power circuit: (80%-115%)
n Un--allows to work continuously.

 